Computational simulation of a diesel generator consuming vegetable oil "in nature" and air enriched with hydrogen



Document title: Computational simulation of a diesel generator consuming vegetable oil "in nature" and air enriched with hydrogen
Journal: Dyna (Medellín)
Database: PERIÓDICA
System number: 000383652
ISSN: 0012-7353
Authors: 1
2
1
Institutions: 1Universidade Federal do Para, Faculdade de Engenharia Eletrica, Belem, Para. Brasil
2Universidade Federal do Para, Faculdade de Engenharia Mecanica, Belem, Para. Brasil
Year:
Season: Mar-Abr
Volumen: 82
Number: 190
Pages: 147-152
Country: Colombia
Language: Inglés
Document type: Artículo
Approach: Aplicado, descriptivo
Spanish abstract Simulamos un generador diesel para operar con aceite de palma e hidrógeno como combustibles. El objetivo era investigar cómo la adición de hidrógeno puede acelerar el final de la combustión de aceite vegetal, y en consecuencia mejorar la eficiencia eléctrica del generador, para la misma tasa de flujo de masa de combustible. Las simulaciones fueron realizadas utilizando el software AVL BOOST y validadas con datos experimentales. El generador fue simulado para operar con 75%, 80% y 100% de la carga utilizando aceite de palma natural, y el hidrógeno comenzó a ser inyectado en el colector de admisión en porciones de 5% a 20% que substituían el combustible principal. Las simulaciones mostraron aumento de la potencia eléctrica, reducción en el consumo específico de combustible y mejora de la eficiencia global de la operación del conjunto generador a una carga de 100%. Resultados satisfactorios de funcionamiento se obtuvieron con carga del 75%
English abstract A diesel generator was simulated operating with palm oil as fuel and hydrogen doping the inlet air. The objective was to investigate how the addition of hydrogen can accelerate the end of vegetable oil combustion, and consequently improve the electrical efficiency of the generator set up, for the same mass flow rate of fuel. The simulations were performed using AVL BOOST software and validated with experimental data. The generator was simulated operating with 75%, 80% and 100% of the nominal load using palm oil in nature, and hydrogen being injected at the intake manifold in parcels of 5% to a maximum of 20% in energy content by replacing the main fuel. The simulations showed increase in electrical power, reduction in specific fuel consumption, improving the overall efficiency of the generator set with 100% load. Good results were obtained with operation at 75% of the nominal load
Disciplines: Ingeniería
Keyword: Ingeniería eléctrica,
Generadores eléctricos,
Combustibles alternativos,
Aceite de palma,
Simulación por computadora
Keyword: Engineering,
Electrical engineering,
Electric generators,
Alternative fuels,
Palm oil,
Computer simulation